THE B.T.H. AUTOMATIC SECTION SWITCH

There were many pieces of anciliary electrical apparatus, one of which was the "Automatic section switch". Below is reprinted the B.T.H. technical data for this interesting device......

 

B.T.H. AUTOMATIC SECTIONALING SWITCH TYPE ASC. 500

REFER DRGS. YD. 33331 AND YD. 33332

 

A device that will prove of considerable value to Transport Organisations facing the question of the equalisation of load distribution on feeders for Traction Systems, has been developed by the B.T.H. Co, of Rugby.

The object of the Switch is to enable more lightly loaded sections to assist adjacent sections more heavily laden. This is of the greatest service at tines of localised peak loads such as football matches, closing tine of works etc.

It also ensures a ready path for regeneration currents to assist nearby loads.

On Trolley Bus systems the negative return circuit bas a higher resistance than on a Tramway System as the track is not available as a return conductor. It is necessary therefore to use every means available for lessening voltage drop on the overhead line, whether this be due to drop on the positive or negative side.

Since the speed of a traction motor is approximately proportional to the voltage available at its terminals, any drop in line volts reduces the speed of the service.

Hitherto, heavy demand for current in certain areas had been associated with lowered voltage, reduced speed of equipment, and possibly irregular operation of the control.

Efforts to meet this difficulty have been made by bridging the section insulators, on the overhead, by hand operated switches in section pillars.

This has meant that the effect of a fault has been far-reaching, and has resulted in the shutting down of a considerable area until the trouble is cleared, or the section isolated by hand.

The B.T.H. Automatic Sectionalising Switch has been developed to meet this particular difficulty.

In effect, it permits of the section insulators being bridged by means of a switch which is normally closed, thus enabling the feeders, distributors, and the overhead to be operated in parallel.

The result is the reduction of feeder losses, the keeping up of line volts, the maintenance of schedule speed, and reliability of control operation.

At the same time, should a fault develop, the defective section is immediately isolated from the rest of the system.

The Automatic Sectionalising Switches open automatically together with the individual feeder breaker feeding that section.

This means immediate localisation of the faulty area and the maintenance of service on the remainder of the system. Immediately the fault has been cleared and the section breaker closed, then the Automatic Sectionalising Switches reclose automatically.

Consider for a moment the delay associated with the bridging of section insulators by hand operated switches in section pillars.

On the occurrence of a fault, a linesman has to be despatched to open section pillars and. clear faulty section by hand.

On clearing the line, these section pillars have to be revisited and the hand operated switches reclosed, if this is omitted all the troubles of delayed schedule and other complaints associated with lowered voltage are reported.

These delays and troubles may be removed by installing the B.T.H. Automatic Sectionalising Switches. These devices open on overload and will not reclose until fault cleared, when they immediately reclose, and this without any attention other than the reclosing of the feeder breaker at the substation controlling the faulty section.

The device, which may be arranged for pole mounting, or erection in a suitable type of section pillar, is self-contained and does not depend on pilot wires or other form of remote control.

It consists primarily of a contactor, the operating coil of which is under control of a relay having a small time lag.

A simple overload relay is arranged to trip open the contactor in the event of trouble on the overhead.

Once opened, the switch will not reclose until potential has been re-established across the section insulator, which is effected by reclosing the section breaker at the substation.

A control switch is incorporated to render the device inoperative if desirable.

To sum up, the installation of these devices -

1) Isolates faulty sections automatically.

2) Makes better use of existing feeders.

3) Maintains speed schedule.

4) Secures greater continuity of supply.

5) Improves bus lighting by keeping up volts.

6) Reduces power distribution losses.

Systems using regenerative braking will appreciate the fact that continuity of the overhead will lessen pressure rises and allow of trolley buses in adjacent sections absorbing the regenerated load, thus levelling out voltage peaks, and increasing the efficiency of the system.

The following technical description of the operation of the device should be read in conjunction with Drawings YD.33331 and YD.33332.

The above drawings show the internal connections as arranged for Double Pole and Single Pole operation respectively, the latter being used where the negative return circuit is earthed, the Single Pole operation being described below.

"F" is a relay of the balanced armature type having two operating coils, each respectively energised from opposite sides of the section insulator separating adjacent substation areas.Any excessive difference of potential between the two coils in either direction, opens the relay contacts.

Approximately equal potentials on both coils allow the relay contacts to close thus completing the operating circuit for the time delay interlock "E".

The closing of "E" completes the circuit for the operating coil of contactor "A" which is the contactor bridging the section insulator.The action of contactor "A" closing, closes an interlock making a retaining circuit for the contactor, and simultaneously other interlocks open the circuit of the time delay interlock and open the circuits of both coils of the balanced relay. Thus it will be noted that once the contactor is closed all circuits are opened except that for the contactor operating coil, which is thus held positively closed by the line potential.

An overload coil "C" in the contactor circuit opens the operating circuit for contactor "A". Thus on a fault occurring in either section, or should any excessive interchange of current take place between one substation end the adjacent one, the contactor "A" -drops open, thus automatically isolating the two sections.When the fault or overload has been removed and potential restored to both sections, then the sequence of operations already described recloses the contactor.It will be noted that under normal operation the contactor is always closed, thus levelling peak loads, providing increased area for absorbing regenerated currents, preventing voltage peaks, and reducing line losses.The relay is adjustable to permit of reclosing of contactor at a per-determined difference of volts on both sides of the section insulator.If one substation is shut down, the adjacent one carries on feeding both sections provided no excessive overload occurs.If it is desired to deaden one section, open both feeder breakers and reclose one; the time delay interlock ensuring that the relay has definitely operated before the contactor operating coil can be energised.A manually operated control switch isolates the operating mechanism for inspection purposes.It is recommended that the device be housed in a feeder pillar of standard design, although pole mounting can be provided. Where current is charged on the maximum demand system per substation, considerable economies are capable of being effected. A special layout of the device could be arranged to meet space available in standard feeder pillar on receipt by us of drawing showing dimensions of maximum panel size capable of being accommodated in the pillar.

 

____________________________________________

 

 Back to the BCMTG home page.